	<frame id="1">
		<textdata>
			<h3>Introduction</h3>
			<p><b>At anytime press the <i>Back</i> button on your web browser to return to the main menu.</b></p>
			<p>Press <font color="#669900"><b><i>Next</i></b></font> to play the next scene and <font color="#CC0000"><b><i>Previous</i></b></font> to repeat the previous scene. Press the <font color="#336699"><b><i>Callout</i></b></font> button on the simulation to toggle on/off the labels.</p>
			<p><i>There is no further introductory information for this simulation.</i></p>
		</textdata>
	</frame>
	<frame id="2">
		<textdata>
			<h3>Condensate return</h3>
			<p>A non-electric pump operates on the positive displacement principle. Pressure, typically supplied by steam, is used to pump high temperature condensate or other liquids. Generally used where electricity is not readily available or in hazardous environments that prohibit use of electrical power.</p>
			<p>Condensate first flows into the <b>receiver</b> (top tank). Condensate then flows, by gravity:</p>
			<ul>
				<li>out the <b>receiver</b> (top tank) drain</li>
				<li>down the interconnected <b>suction piping</b></li>
				<li>through the <b>suction inlet (<i>swing</i>) check valve</b></li>
				<li>into the inlet of the <b>pump body</b> (bottom tank)</li>
			</ul>
			<p>Back pressure keeps the <b>discharge (<i>spring-loaded</i>) check valve</b> closed preventing condensate from flowing out the discharge outlet of the <b>pump body</b>. As the body fills with liquid, the float rises and the water level of the receiver falls. During the filling phase:</p>
			<ul>
				<li>the <b>steam inlet</b> is closed</li>
				<li>the <b>exhaust vent</b> is open</li>
				<li>the <b>suction inlet (<i>swing</i>) check valve</b> is open</li>
				<li>the <b>discharge (<i>spring-loaded</i>) check valve</b> is closed</li>
			</ul>
		</textdata>
	</frame>
	<frame id="3">
		<textdata>
			<h3>Steam enters</h3>
			<p>When the float reaches the high water position (i.e., trip point), the spring of the float mechanism is released which begins the pumping phase. At the trip point, the <b>steam inlet</b> is opened allowing steam to enter into the top portion of the <b>pump body</b>. Simultaneously, the <b>exhaust vent</b> is closed allowing the internal pressure to increase within the <b>pump body</b>.</p>
		</textdata>
	</frame>
	<frame id="4">
		<textdata>
			<h3>Condensate discharged</h3>
			<p>As the internal pressure increases within the <b>pump body</b>, the <b>suction inlet (<i>swing</i>) check valve</b> is closed stopping gravity flow of condensate into the <b>pump body</b> and causing the water level in the <b>receiver</b> to rise.</p>
			<p>Simultaneously, at the high water trip point, the <b>discharge (<i>spring-loaded</i>) check valve</b> opens starting the pumping phase as the pressure within the <b>pump body</b> exceeds the back pressure on the <b>discharge (<i>spring-loaded</i>) check valve</b> -- thus pushing the condensate out the discharge pipe. The water level with in the <b>pump body</b> begins to fall, along with the float.</p>
		</textdata>
	</frame>
	<frame id="5">
		<textdata>
			<h3>Steam vented</h3>
			<p>When the float reaches the low water trip point, the float mechanism reverses action. The <b>steam inlet</b> closes and the <b>exhaust vent</b> opens venting the internal pressure within the <b>pump body</b> to atmosphere. The venting equalizes the internal pressure of the pump with external pressure allowing gravity flow of condensate to resume into the <b>pump body</b>. The fill/pump cycle repeats.</p>
		</textdata>
	</frame>